SmartGuard-63A-T0-AUT0 | Huawei Smart Guard-Whole Home Backup Specs | Huawei FusionSolar

HUAWEI SmartGuard

HUAWEI SmartGuard

HUAWEI SmartGuard-63A-T0/AUTO

HUAWEI SmartGuard-63A-TO/AUTO
HUAWEI SmartGuard-63A-TO/AUTO
HUAWEI SmartGuard-63A-TO/AUTO
Technical Specification
SmartGuard-63A-T0
SmartGuard-63A-AUT0
General Data
arrow
Dimensions (W x H x D)
600 mm × 170 mm × 490 mm
Weight (not including mounting plate)
17 kg
Performance
arrow
AC voltage (nominal)
380 / 400 / 415 V, 220 / 230 / 240 V, L1 / L2 / L3 / N + PE
Max. current (from / to Grid)
63 A
Max. current (from / to Inverter)
60 A
Max. current (to Backup Load)
63 A
Max. current (to Non-BackupLoad)1
63 A
Low-Voltage ride-through
Supported
Switchover time
≤ 20 ms (MAP0), ≤ 100 ms (M1 / MB0)2
Bypass operation mode
Manual
DG mode
Remote control
Interface
arrow
Power output
9.5 - 13.2 V @ 100 mA, ≤ 3 m
LAN
10 / 100 Mbps, ≤ 100 m
WAN
10 / 100 Mbps, ≤ 100 m
WLAN
AP Mode, 802.11b/g/n (2.412 GHz - 2.484 GHz)
RS485
9600 / 19,200 / 115,200 bps, × 2, ≤ 50 m
Digital input
× 2, ≤ 20 m; Avtive port3
Digital output
× 2, ≤ 2 0m
DG Do Port
Passive Port, 1 - 100 mA ≤ 24 V
ATS
Need prepare the ATS, which supports automatic control and automatic switch-in and reset.
Measurement Range
arrow
Current range
≤ 63 A
Energy accuracy
± 1%
Device Management
arrow
Smart energy controllers
up to 3
Smart chargers
up to 2
Heat pump
up to 14
Shelly device
up to 20
Environment
arrow
Cooling
Natural Convection
Relative humidity range
5% - 95% RH (non condensing)
Max. operating altitude
4000 m (derated over 2000 m)
Degree of protection
IP55
Operating temperature range
-25 °C - 50 °C5
Compatible Device
arrow
Smart energy controller
SMax. 3 inverters supported in parallel connection (MAP0)
Max. 1 inverter supported (M1 / MB0)
Smart charger
SCharger–7KS / 22KT–S0
Heat pump
SG-ready
Shelly device
Shelly Plus Plug S, Shelly Plus 2PM, Shelly Pro 2PM 6

*1 The sum of the output current of the backup port and the non backup port could not be more than 63 A.

*2 Seamless switching is disabled by default and needs to be manually enabled.

*3 The position feedback signal must be a passive port that works with an external circuit and can work at a current of less than or equal to 0.7 mA@12 V. The low impedance of the circuit for the position feedback signal is less than or equal to 100 ohms.

*4 1 SG ready Heat Pump can be connected directly. Others can be connected via shelly devices.

*5 On grid Mode: 25 – 30 °C, no derating; 30 – 50 °C, linear derating from 63 A to 43 A; Off grid Mode: 25 – 40 °C, no derating; 40 – 50 °C, linear derating from 60 A to 50 A

*6 The supported firmware version of shelly devices can be found in user manual.

*7 Disclaimer: The preceding values are measured by an internal laboratory of Huawei in a specific environment. The actual values may vary with products, software versions, usage conditions, and environmental factors.