SUN2000-50KTL-M3

SUN2000-50KTL-M3

SUN2000-50KTL-M3
SUN2000-50KTL-M3
SUN2000-50KTL-M3

SUN2000-50KTL-M3

Technical Specification SUN2000-50KTL-M3
Efficiency specs-icon
Max. efficiency 98.5%
European efficiency 98.0%
Input specs-icon
Max. input voltage 1 1100 V
Max. current per MPPT 30 A
Max. current per input 20 A
Max. short circuit current per MPPT 40 A
Start voltage 200 V
MPPT operating voltage range 2 200 V ~ 1000 V
Rated input voltage 600 V
Number of inputs 8
Number of MPP trackers 4
Output specs-icon
Rated AC active power 50,000 W
Max. AC apparent power 55,000 VA
Max. AC active power (cosφ=1) 55,000 W
Rated output voltage 400 Vac / 480 Vac, 3W+(N) + PE
Rated AC grid frequency 50 Hz / 60 Hz
Rated output current 72.2 A @ 400Vac, 60.1 A @ 480Vac
Max. output current 79.8 A @ 400Vac, 66.5 A @ 480Vac
Adjustable power factor range 0.8 LG ... 0.8 LD
Max. total harmonic distortion <3%
Protection specs-icon
Input-side disconnection device Yes
Anti-islanding protection Yes
AC overcurrent protection Yes
DC reverse-polarity protection Yes
PV-array string fault monitoring Yes
DC surge arrester Type II
AC surge arrester Type II
DC insulation resistance detection Yes
Residual current monitoring unit Yes
Arc fault protection Yes
Ripple receiver control Yes
Integrated PID recovery 3 Yes
Communication specs-icon
Display LED Indicators, WLAN + APP
RS485 Yes
Smart dongle WLAN / Ethernet via Smart Dongle-WLAN-FE (Optional)
4G / 3G / 2G via Smart Dongle-4G (Optional)
Monitoring BUS (MBUS) Yes (Isolation Transformer required)
Optimizer Compatibility specs-icon
DC MBUS compatible optimizer 4 MERC-1100/1300W-P
General Data specs-icon
Dimensions (W x H x D) 640 x 530 x 270 mm (25.2 x 20.9 x 10.6 inch)
Weight (with mounting plate) 49 kg (108.1 lb)
Operating temperature range -25 °C ~ 60 °C (-13 °F ~ 140 °F)
Cooling method Smart Air Cooling
Max. operating altitude 4000 m (13,123 ft.)
Relative humidity 0% RH ~ 100% RH
DC connector Amphenol HH4
AC connector Waterproof Connector + OT/DT Terminal
Protection degree IP 66
Topology Transformerless
Nighttime power consumption ≤ 5.5W
Standard Compliance (More Available Upon Request) specs-icon
Safety EN 62109-1/-2, IEC 62109-1/-2, IEC 62116, IEC 60068, IEC 61683
Grid connection standards IEC 61727, VDE-AR-N4105, VDE 0126-1-1, BDEW, G59/3, UTE C 15-712-1, CEI 0-16, CEI 0-21, RD 661, RD 1699,
P.O. 12.3,RD 413, EN-50438-Turkey, EN-50438-Ireland, C10/11, MEA, Resolution No.7,
NRS 097-2-1, DEWA

1. The maximuminput voltage is the upper limit of the DC voltage. Any higher input DC voltage would probably damage inverter.

2. Any DC input voltage beyond the operating voltage range may result in inverter improper operating.

3. SUN2000-50KTL-M3 raises potential between PV- and ground to above zero through integratedPID recovery functionto recover module degradation from PID. Supported module types include: P-type (mono, poly), N-type (nPERT, HIT)