The fuse inside the Energy Storage Module cannot be replaced separately. This section describes how to replace the fuse of the Energy Storage Control Unit.
Prerequisite for replacing the fuse: If the inverter is faulty, the fuse is likely to be damaged. In this case, check whether the fuse is damaged. If yes, replace the fuse.
Before the replacement, power off the system.
Table 1-1 Fuse specifications
Fuse | Required Specifications | ||
Category | Lower Limit | Typical Value | Upper Limit |
Component type | - | Fuse | - |
Fuse type | - | Fast blow fuse | - |
Rated voltage (V AC/DC) | 1100 V DC | - | - |
Rated current | 38 A | - | - |
Breaking capacity | 10 kA | - | - |
Nominal fusing heat I2T | 600 | - | 1400 |
Cold resistance value | - | - | 0.005 Ω |
Package dimensions (the dimension tolerance shall be specified in the specifications provided by the supplier) | - | 14.3 mm x 51 mm | - |
Table 1-2 Fuse model
No. | Fuse Model | Manufacturer |
1 | 0828040.UXTHP | LITTELFUSE |
2 | FWL-38A14F | Cooper Xi'An Fusegear |
3 | RS309-MM-14C43A | Sinofuse Electric |
Do not store batteries for extended periods of time. The deep discharge during storage may damage batteries. If you have to store batteries, observe the following storage requirements.
Table 1-3 Lithium battery charge intervals
Required Storage Temperature | Actual Storage Temperature | Charge Interval | Remarks |
–10°C < T ≤ +55°C | T ≤ –10°C | Not allowed |
• Not reaching the time for charge: Use the batteries as soon as possible. • Reaching the time for charge: Charge the batteries. • Batteries can be charged for a maximum of three times during storage. Dispose of batteries if the maximum charge times are exceeded. • The batteries must be charged to at least 50% SOC. Same as factory SOC. |
–10°C < T ≤ +25°C | 15 months | ||
25°C < T ≤ 35°C | 9 months | ||
35°C < T ≤ 55°C | 6 months | ||
T > 55°C | Not allowed |
1. Dispose of deformed, damaged, or leaking batteries directly irrespective of how long they have been stored.
2. The storage duration starts from the latest charge time labeled on the battery package. If a battery is qualified after charge, update the latest charge time and the next charge time (Next charge time = Latest charge time + Charge interval) on the label.
After logging in to the inverter, if the FusionSolar app detects that the LUNA2000 firmware version is outdated, the app prompts you to upgrade the LUNA2000. You can choose immediate activation or delayed activation. If you choose immediate activation, the LUNA will be upgraded immediately after the firmware package is uploaded. If you choose delayed activation, the activation of the firmware will be performed four hours after you log out of the app.
NOTICE
You need to cover the related transportation expenses.
• The baud rate of MB0 series inverter is 115200, that of the M1 series inverter is 9600, and the default baud rate of S1 is "9600". When S1 is connected to SUN2000-(12K-25K)-MB0, its baud rate will be automatically increased to 115200, so the S1's baud rate needs to be restored to 9600 before powering off the system, otherwise, the baud rate of S1 remains unchanged as 115200, and when using it with the M1 inverter, the baud rate will show inconsistent leading to communication failure.
• Steps: Use the Huawei FusionSolar App to scan the QR code to connect to the inverter, go to the Communication Configuration page, and select RS485 > Baud Rate Negotiation > RS485_2 > Baud Rate Negotiation > Restore to 9600.